• Before you activate the automatic fault reset or automatic restart functions of the drive
control program, make sure that no dangerous situations can occur. These functions
reset the drive automatically and continue operation after a fault or supply break. If these
functions are activated, the installation must be clearly marked as defined in
IEC/EN 61800-5-1, subclause 6.5.3, for example, "THIS MACHINE STARTS
AUTOMATICALLY".
• The maximum drive power cycles is five times in ten minutes. Power cycling the drive
too often can damage the charging circuit of the DC capacitors.
• Validate any safety circuits (for example, Safe torque off or emergency stop) in start-up.
See separate instructions for the safety circuits.
• Beware of hot air exiting from the air outlets.
• Do not cover the air inlet or outlet when the drive is running.
Note:
• If you select an external source for the start command and it is on, the drive will start
immediately after fault reset unless you configure the drive for pulse start. See the
firmware manual.
• Depending on the wiring and parametrization of the drive, the stop key on the control
panel may not stop the drive.
• Only authorized persons are allowed to repair a malfunctioning drive.
18 Safety instructions