PE (grounding)T1/U2, T2/V2, T3/W2L1, L2, L3Frame
size
Tighten-
ing torque
lbf·ft
Bolt sizeTighten-
ing torque
lbf·ft
Max. wire
size
AWG
Min. wire
size
1)
AWG
Tighten-
ing torque
lbf·ft
Bolt sizeMax. wire
size
AWG
29.5M10 (3/8")22.13×300
MCM
322.1M10 (3/8")3×300
MCM
R6
29.5M10 (3/8")22.13×500
MCM
3/022.1M10 (3/8")3×500
MCM
R7
29.5M10 (3/8")22.12×(3×300
MCM)
2×1/0 /
2×3/0
2)
22.1M10 (3/8")2×(3×300
MCM)
R8
29.5M10 (3/8")51.62×(3×500
MCM)
2×3/051.6M12
(7/16")
2×(3×500
MCM)
R9
29.5M10 (3/8")51.64×(3×300
MCM)
-51.6M12
(7/16")
4×(3×300
MCM)
R10
29.5M10 (3/8")51.64×(3×500
MCM)
-51.6M12
(7/16")
4×(3×500
MCM)
R11
1)
Note: Minimum wire size does not necessarily have enough current capability for full load.
Make sure the installation complies with local laws and regulations.
2)
-01-246A-4: 2×1/0, -01-293A-4: 2×3/0
US With option +E205
Input and motor cable terminal bolt sizes, maximum accepted wire sizes (per three phases)
and tightening torques are given below.
PE (grounding)L1, L2, L3, U2, V2, W2Frame size
Tightening
torque
N·m
Bolt size
mm
2
Tightening
torque
N·m
Bolt sizeMax. wire size
mm
2
30…44M1022.1M10 (3/8")3×300 MCMR6
30…44M1022.1M10 (3/8")3×500 MCMR7
30…44M1051.6M12 (7/16")2×(3×300 MCM)R8
30…44M1051.6M12 (7/16")2×(3×500 MCM)R9
30…44M1051.6M12 (7/16")4×(3×300 MCM)R10
30…44M1051.6M12 (7/16")4×(3×500 MCM)R11
Technical data 183