Compliance with the EN 61800-3:2004
Definitions
EMC stands for Electromagnetic Compatibility. It is the ability of electrical/electronic
equipment to operate without problems within an electromagnetic environment. Likewise,
the equipment must not disturb or interfere with any other product or system within its locality.
First environment includes establishments connected to a low-voltage network which supplies
buildings used for domestic purposes.
Second environment includes establishments connected to a network not supplying domestic
premises.
Drive of category C3: drive of rated voltage less than 1000 V and intended for use in the
second environment and not intended for use in the first environment.
Drive of category C4: drive of rated voltage equal to or above 1000 V, or rated current equal
to or above 400 A, or intended for use in complex systems in the second environment.
Category C2
The drive frames R6 to R9 comply with the standard with the following provisions:
1. The motor and control cables are selected as specified in the hardware manual.
2. The drive is installed according to the instructions given in the hardware manual.
3. Maximum motor cable length is 150 meters.
WARNING!
The drive may cause radio interference if used in a residential or domestic
environment. The user is required to take measures to prevent interference, in
addition to the requirements for CE compliance listed above, if necessary.
Note:
Do not install a drive equipped with EMC filter on IT (ungrounded) systems. The supply
network becomes connected to ground potential through the EMC filter capacitors which
may cause danger or damage the unit.
Category C3
The drive complies with the standard with the following provisions:
1. The motor and control cables are selected as specified in the hardware manual.
2. The drive is installed according to the instructions given in the hardware manual.
3. Maximum motor cable length is 100 meters.
WARNING!
A drive of category C3 is not intended to be used on a low-voltage public network
which supplies domestic premises. Radio frequency interference is expected if
the drive is used on such a network.
Category C4
If the provisions under Category C3 cannot be met, the requirements of the standard can
be met as follows:
1. It is ensured that no excessive emission is propagated to neighboring low-voltage
networks. In some cases, the natural suppression in transformers and cables is sufficient.