EasyManua.ls Logo

ABB ACS580-07 - Safety Data; Abbreviations

ABB ACS580-07
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety data
The safety data for the Safe torque off function is given below.
Note:
The safety data is calculated for redundant use, and does not apply if both STO channels
are not used.
T
M
(a)
CCFHFTSCCat.
DC
(%)
MTTF
D
(a)
PFD
avg
(T
1
= 5 a)
PFD
avg
(T
1
= 2 a)
PFH
(T
1
= 20 a)
(1/h)
SFF
(%)
PL
SIL/
SILCL
Frame size
2080133≥9093808.58E-053.44E-053.92E-09>99e3
R6
R7
2080133≥9087928.84E-053.69E-054.22E-09>99e3
R8
R9
2080133≥90175449.08E-053.63E-054.15E-0999.60e3
R10
R11
3AXD10000015777 K, 3AXD10000410558 D
The following temperature profile is used in safety value calculations:
670 on/off cycles per year with ΔT = 71.66 °C
1340 on/off cycles per year with ΔT = 61.66 °C
30 on/off cycles per year with ΔT = 10.0 °C
32 °C board temperature at 2.0% of time
60 °C board temperature at 1.5% of time
85 °C board temperature at 2.3% of time.
Relevant failure modes:
The STO trips spuriously (safe failure)
The STO does not activate when requested
A fault exclusion on the failure mode “short circuit on printed circuit board” has been
made (EN 13849-2, table D.5). The analysis is based on an assumption that one
failure occurs at one time. No accumulated failures have been analyzed.
STO response times:
STO reaction time (shortest detectable break): 1 ms
STO response time: 2 ms (typical), 5 ms (maximum)
Fault detection time: Channels in different states for longer than 200 ms
Fault reaction time: Fault detection time + 10 ms
Indication delays:
STO fault indication (parameter 31.22) delay: < 500 ms
STO warning indication (parameter 31.22) delay: < 1000 ms
Abbreviations
DescriptionReferenceAbbr.
Classification of the safety-related parts of a control system in respect
of their resistance to faults and their subsequent behavior in the fault
condition, and which is achieved by the structural arrangement of the
parts, fault detection and/or by their reliability. The categories are: B,
1, 2, 3 and 4.
EN ISO 13849-1Cat.
Common cause failure (%)EN ISO 13849-1CCF
The Safe torque off function 255