Parameter setting example for frequency output
This example shows how to make digital output DO1 of the extension module indicate the
motor speed 0... 1500 rpm with a frequency range of 0...10000 Hz.
SettingParameter
Frequency output15.22 DO1 configuration
01.01 Motor speed used15.33 Freq out 1 source
015.34 Freq out 1 src min
1500.0015.35 Freq out 1 src max
1000 Hz15.36 Freq out 1 at src min
10000 Hz15.37 Freq out 1 at src max
■ Diagnostics
Faults and warning messages
Warning A7AB Extension I/O configuration failure.
LEDs
The extension module has one diagnostic LED.
DescriptionColor
The extension module is powered up.Green
Optional I/O extension modules 277