Type designation label
The type designation label includes an IEC rating, appropriate markings, a type designation
and a serial number, which allow identification of each unit. The type designation label is
located on the front cover. An example label is shown below.
1
2
3
4
6
8
9
7
5
Type designation, see section Type designation key below.
1
Manufacturing address2
Frame size3
Cooling method4
Degree of protection5
Ratings, see section Ratings (page 171), Electrical power network specification (page 211) and Motor
connection data (page 211).
6
Short-circuit withstand strength, see section Electrical power network specification (page 211).
7
Valid markings8
Serial number. The first digit of the serial number refers to the manufacturing plant. The next four digits
refer to the unit’s manufacturing year and week, respectively. The remaining digits complete the serial
number so that there are no two units with the same number.
9
Type designation key
The type designation contains information on the specifications and configuration of the
drive. The first digits from left express the basic configuration (eg, ACS580-07-0640A-4).
The optional selections are given thereafter, separated by plus signs, eg, +B055. The main
selections are described below. Not all selections are available for all types or with all options.
For more information, refer to ACX580-07 Ordering Information (3AXD10000485076 available
on request).
DescriptionCode
Basic codes
Product seriesACS580
When no options are selected: cabinet-installed drive, IP21, main switch, AC fuses, ACS-AP-S as-
sistant control panel, for frames R6 to R9 EMC filtering for first environment TN grounded systems
(category C2), for frames R10 and R11 EMC filtering for second environment TN grounded systems
(category C3), input choke, common mode filter in frames R10 and R11, coated boards, ACS580
standard control program, EIA/RS-485 fieldbus connector, Safe torque off function, bottom entry
and exit of cables, multilingual device label sticker, USB memory stick containing all manuals.
07
Size
Refer to the rating tables, Ratings (page 171)
xxxx