Put the connector back onto the terminal post. Start the combi screw, and
turn it at least two rotations by hand.
WARNING!
Before using tools, make sure that the nut/screw is not cross-threading.
Cross-threading will damage the drive and cause danger.
Tighten the combi screw to a torque of 30 N·m (22 lbf·ft).
Tighten the conductor(s) to 40 N·m (30 lbf·ft) for frame R8 or to 70 N·m
(52 lbf·ft) for frame R9.
11. Frames R8…R9: If you install parallel cables, install the second grounding shelf
for the parallel power cables (11a). Repeat steps 6…11 (11b).
R8…R9R8…R9
11a
11b
M5×25
M5×12
11a
11b
12. Install the grounding shelf of the control cables.
13. Reinstall the shroud on the power terminals.
14. Secure the cables outside the unit mechanically.