DescriptionTermConnection
Ready runRO1C19
19
20
21
22
23
24
25
26
27
Ready run status
Run status
Fault status
250 V AC / 30 V DC
2 A
RO1A20
RO1B21
Running
250 V AC / 30 V DC
2 A
RO2C22
RO2A23
RO2B24
Fault (-1)
250 V AC / 30 V DC
RO3C25
RO3A26
2 A
RO3B27
X5 EIA-485 Modbus RTU
Embedded Modbus RTU (EIA-485)
B+29
29
30
31
S4
S5
A-30
DGND31
Serial data link termination switchTERMS4
Serial data link bias resistors switchBIASS5
X4 Safe Torque Off
Safe torque off. Factory connection.
Both circuits must be closed for the
drive to start. Refer to The Safe torque
off function (page 409).
OUT134
34
35
36
37
38
6)
6)
OUT235
SGND36
IN137
IN238
X10 24 V AC/DC
External 24 V AC/DC input to power
up the control unit when the main
supply is disconnected.
9)
24 V
AC/DC+
in
40
40
41
24 V
AC/DC- in
41
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).
Digital inputs DI1…DI5 also support 10…24 V AC.
Terminal sizes (all terminals): 0.14 2.5 mm
2
(26…14 AWG)
Tightening torques: 0.5 0.6 N·m (4.4 5.3 lbf·in)
Wire strip length 7…8 mm (0.3 in)
Control unit 221