Derating factor (k) for the minimum switching frequen-
cies at 40 °C (+104 °F)
ACS580-01-…Frame
size
12 kHz8 kHz4 kHz2 kHz1 kHz
0.500.660.8311242A-6R9
0.500.660.7411271A-6R9
Switching frequency derating with actual output current values
These tables show the output current values with different switching frequencies.
Note that other derating factors, for example ambient temperature and altitude,
may also affect to the output current.
IEC
Nominal output current (
I
2
) for the minimum switching
frequencies at 40 °C (+104 °F)
Nominal
output
ACS580-
01-…
Frame
size
16 kHz12 kHz8 kHz4 kHz2 kHz1 kHz
I
2
AAAAAAA
3-phase
U
n
= 230 V
3.43.84.24.74.74.74.704A7-2R1
4.85.46.06.76.76.76.706A7-2R1
5.56.16.87.67.67.67.607A6-2R1
8.69.610.712.012.012.012.0012A-2R1
12.113.515.016.916.916.918.0018A-2R1
15.918.121.124.524.524.524.5025A-2R2
20.323.126.831.231.231.231.2032A-2R2
29.433.639.746.746.746.746.7047A-2R3
37.843.25160606060060A-2R3
52617389898989089A-2R5
-42.85991919191091A-2R4
677994115115115115115A-2R5
101115130144144144144144A-2R6
120137154171171171171171A-2R7
149170192213213213213213A-2R7
N/AN/AN/AN/A248248248248A-2R8
N/AN/AN/A276276276276276A-2R8
286 Technical data