12. For 480 V and 600 V drives: When designing UL508A panels, Article SB 4.2.3
Exception No. 3 allows the use of other manufacturers' current limiting inverse
time circuit breakers which have same voltage, current and interrupting rating,
if
I
peak
and
I
2
t
are the same or less than the ABB specified circuit breaker.
13. For 480 V and 600 V drives: Do not use non-current limiting inverse time circuit
breakers.
14. For 480 V drives: Enclosures for frames R1, R3, and R9 must have a solid bottom
directly below the drive. i.e. fans, filters or louvers cannot be mounted directly
below the drive but can be mounted in adjacent areas on the bottom of the
enclosure.
15. For 480 V drives: Enclosures for frame R6 must have a solid top directly above
the drive. Fans, filters our louvers cannot be mounted directly above the drive.
16. For 480 V drives: Only R8 frame drives with serial numbers beginning
1204301926 when built in Finland and 2205002140 when built in the U.S. may
be protected with circuit breakers listed in the tables above.
17. For 480 V drives: Only R9 frame drives with serial numbers beginning
1204109256 when built in Finland and beginning 22106xxxxx when built in the
U.S. may be protected with circuit breakers listed in the tables above.
18. For 600 V drives: Enclosures for frames R2, R3, R5 and R9 must have a solid
bottom directly below the drive. i.e. fans, filters or louvers cannot be mounted
directly below the drive but can be mounted in adjacent areas on the bottom
of the enclosure.
19. You can use alternative circuit breakers if they meet certain characteristics.
For acceptable breakers, refer to Branch Circuit Protection for ABB drives
manual supplement (3AXD50000645015 [English]).
Dimensions, weights and free space requirements
Dimensions and weightsFrame
size
UL Type 1IP21
WeightDWH4H3H2H1WeightDWH4H3H2H1
lbininininininkgmmmmmmmmmmmm
10.18.784.9213.0314.69--4.6223125331373--R1
14.69.004.9217.0118.62--6.6229125432473--R2
26.09.027.9919.2917.87-
*)
-
*)
11.8229203490454-
*)
-
*)
R3
41.910.127.9925.0423.62-
*)
-
*)
19.0257203636600-
*)
-
*)
R4
44.110.127.9925.0423.66-
*)
-
*)
20.0257203636601-
*)
-
*)
R4 v2
62.411.617.9924.9028.8223.4623.4628.3295203633732596596R5