R+, R-, UDC+ and UDC- terminalsCable entriesFrame
size
T (Wire screw)Max wire size
(solid/stranded)
Min wire size
(solid/stran-
ded)
2)
Ø
1)
Per cable
type
N·mScrew/Boltmm
2
mm
2
mmpcs
5.5M5701.5/1.5391R4 v2
15M5706391R5
30M815025451R6
30M1024095541R7
40M102×1502×50452R8
3-phase
U
n
= 400 or 480 V
1.0
3)
6/40.20/0.25231R1
1.5
3)
16/160.5/0.5231R2
3.5
3)
35/250.5/0.5231R3
4.0
3)
500.5/0.5391R4
5.5
3)
701.5/1.5391R4 v2
15M5706391R5
30M815025451R6
30M1024095541R7
40M102×1502×50452R8
70M122×2402×95542R9
1)
Maximum cable diameter accepted. For the entry plate hole diameters, see chapter Dimension
drawings (page 363).
2)
Note: Minimum wire size does not necessarily have enough currentc apability for full load. Make sure
the installation complies with local laws and regulations.
3)
Either cable lug (R5) or clamp (R6…R9) is used for grounding.
Screwdrivers for the terminals of the main circuitFrame size
Combo: Slot 4 mm and PH1R1
Combo: Slot 4.5 mm and PH2R2
PH2R3, R4
TorxR4 v2
332 Technical data