UL (NEC)
Input (except IP66 (UL Type 4X) with disconnect), motor, resistor and DC cable
entries, maximum wire sizes (per phase) and terminal screw sizes and tightening
torques (
T
) are given below.
Grounding terminalsL1,L2, L3, T1/U, T2/V, T3/W terminalsCable
entries
Frame
size
T
Wire range (stranded/sol-
id)
T
Wire range (stranded/solid)
2)
Ø
1)
Per
cable
type
MaxMinMaxMin
lbf·ftAWGAWGlbf·ftAWGAWGinpcs
3-phase
U
1
= 200…240 V,
P
n
at
U
n
= 208/230 V, 60 Hz
1.16180.710241.381R1
1.16181.16201.381R2
1.12182.62201.731R3
2.12123.01201.981R4
2.12124.01202.011R4 v2
1.6
3)3)
11.11/062.011R5
7.2350 MCM
3)
22.1300 MCM42.441R6
7.2350 MCM
3)
29.5500 MCM3/02.991R7
7.22×350 MCM
3)
29.52×300 MCM2×1/02.442R8
7.22×350 MCM
3)
51.62×500 MCM2×3/02.442R9
3-phase
U
1
= 440…480 V,
P
n
at
U
n
= 480 V, 60 Hz
1.16180.710241.381R1
1.16181.16201.381R2
1.12182.62201.731R3
2.12123.01201.981R4
2.12124.01202.011R4 v2
1.6
3)3)
11.11/062.011R5
7.2350 MCM
3)
22.1300 MCM42.441R6
7.2350 MCM
3)
29.5500 MCM3/02.991R7
7.22×350 MCM
3)
29.52×300 MCM2×1/02.442R8
7.22×350 MCM
3)
51.62×500 MCM2×3/02.442R9
Technical data 333