Loading...
AI cable type
1)
,
2)
Cu cable type
1)
Frame sizeACS580-01-…
mm
2
mm
2
-3×2.5 + 2.5R112A7-4
-3×2.5 + 2.5R2018A-4
-3×6 + 6R2026A-4
-3×10 + 10R3033A-4
-3×10 + 10R3039A-4
-3×10 + 10R3046A-4
-3×25 + 16R4, R4 v2062A-4
-3×35 + 16R4, R4 v2073A-4
-3×50 + 25R5088A-4
-3×50 + 25R4 v2089A-4
-3×70 + 35R5106A-4
-3×95 + 50R6145A-4
-3×120 + 70R7169A-4
-3×150 + 70R7206A-4
-2×(3×70+35)R8246A-4
-2×(3×95+50)R8293A-4
-2×(3×120+70)R9363A-4
-2×(3×150+70)R9430A-4
1)
The cable sizing is based on max. 6 cables laid on a cable ladder side by side, ambient temperature 30
°C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364- 5-52/2001). For other
conditions, size the cables according to local safety regulations, appropriate input voltage and the
load current of the drive. See page 330 for the accepted cable sizes of the drive.
2)
Aluminum cables can be used with
U
n
= 230 V frames R5…R8 only.
Typical power cables UL (NEC)
Cu cable typeFrame sizeACS580-01-…
AWG/kcmil
3-phase
U
1
= 200…240 V,
P
n
at
U
n
= 208/230 V, 60 Hz
14R104A6-2
14R106A6-2
14R107A5-2
14R110A6-2