Diagnostics
LEDs
The adapter module has one diagnostic LED.
DescriptionColor
The adapter module is powered up.Green
There is no communication with the drive control unit or the adapter
module has detected an error.
Red
■
Technical data
Into slot 2 of drive control unitInstallation
IP20 / UL 1 TypeDegree of protection
See the drive technical data.Ambient conditions
CardboardPackage
Analog inputs (80..82, 83..85, 86..88)
1.5 mm
2
Maximum wire size
-11 V … +11 VInput voltage ( AI+ and AI-)
-22 mA … +22 mAInput current ( AI+ and AI-)
>200 kohm (voltage mode), 100 ohm (current
mode)
Input resistance
Optional cable shield connections
Analog outputs (90..92, 93..95)
1.5 mm
2
Maximum wire size
0 V … +11 VOutput voltage (AO+ and AO-)
0 mA … +22 mAOutput current (AO+ and AO-)
< 20 ohmOutput resistance
>10 kohmRecommended load
± 1% Typical, ± 1.5% Max of full-scale valueInaccuracy
Optional cable shield connections
Optional I/O extension and adapter modules 435