3. Set the parameters of the extension module to applicable values.
Parameter setting example for relay output
This example shows how make the relay output RO4 of the extension module
indicate the reverse direction of rotation of the motor with a one-second delay.
SettingParameter
Reverse15.07 RO4 source
1 s15.08 RO4 ON delay
1 s15.09 RO4 OFF delay
■
Fault and warning messages
Warning A7AB Extension I/O configuration failure.
■
Technical data
Into an option slot on the drive control unitInstallation
IP20 / UL Type 1Degree of protection
See the drive technical data.Ambient conditions
CardboardPackage
Reley outputs (50…52, 53…55)
1.5 mm
2
Maximum wire size
12 V / 10 mAMinimum contact rat-
ing
250 V AC / 30 V DC / 2 AMaximum contact
rating
1500 VAMaximum breaking
capacity
115/230 V inputs (70…78)
1.5 mm
2
Maximum wire size
115 to 230 V AC ±10%Input voltage
2 mAMaximum current
leakage in digital off
state
Isolation areas
446 Optional I/O extension and adapter modules