148 Parameters
01.14 Output power Drive output power. The unit is selected by parameter 96.16
Unit selection. A filter time constant for this signal can be
defined by parameter 46.14 Filter time power.
-
-32768.00…
32767.00 kW or hp
Output power. 1 = 1 unit
01.15 Output power % of
motor nom
Output power in percent of the nominal motor power. -
-300.00… 300.00% Output power. 1 = 1%
01.16 Output power % of
drive nom
Output power in percent of the nominal drive power. -
-300.00… 300.00% Output power. 1 = 1%
01.17 Motor shaft power Estimated mechanical power at motor shaft. -
-32768.00…
32767.00 kW or hp
Motor shaft power. 1 = 1 unit
01.18 Inverter GWh
counter
Amount of energy that has passed through the drive (in either
direction) in full gigawatt-hours. The minimum value is zero.
-
0…65535 GWh Energy in GWh. 1 = 1 GWh
01.19 Inverter MWh
counter
Amount of energy that has passed through the drive (in either
direction) in full megawatt-hours. Whenever the counter rolls
over, 01.18 Inverter GWh counter is incremented. The
minimum value is zero.
-
0…1000 MWh Energy in MWh. 1 = 1 MWh
01.20 Inverter kWh
counter
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. Whenever the counter rolls
over, 01.19 Inverter MWh counter is incremented. The
minimum value is zero.
-
0…1000 kWh Energy in kWh. 10 = 1 kWh
01.24 Flux actual % Used flux reference in percent of nominal flux of motor. -
0…200% Flux reference. 1 = 1%
01.30 Nominal torque
scale
Torque that corresponds to 100% of nominal motor torque.
The unit is selected by parameter 96.16 Unit selection.
Note: This value is copied from parameter 99.12 Motor
nominal torque if entered. Otherwise the value is calculated
from other motor data.
-
0.000…4000000
N·m or lb·ft
Nominal torque. 1 = 100 unit
01.50 Current hour kWh Current hour energy consumption. This is the energy of the
last 60 minutes (not necessarily continuous) the drive has
been running, not the energy of a calendar hour. The value is
set to the value before the power cycle when the drive is
again up and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
01.51 Previous hour kWh Previous hour energy consumption. The value 01.50 Current
hour kWh is stored here when its values has been cumulated
for 60 minutes. The value is set to the value before the power
cycle when the drive is again up and running.
-
0.00… 1000000.00
kWh
Energy. 1 = 1 kWh
No. Name/Value Description Def/FbEq16
ACS580 FW.book Page 148 Wednesday, September 21, 2016 9:48 PM