46 Control system and interfaces
XPOW
External power input
1
+24VI
2
GND
XAI
Reference voltage and analog inputs
1
+VREF 10 VDC, R
L
1…10 kohm
2
-VREF -10 VDC, R
L
1…10 kohm
3
AGND Ground
4
AI1+
5
AI1-
6
AI2+
7
AI2-
XAO
1
AO1
2
AGND
3
AO2
4
AGND
11
NC
12
COM
13
NO
21
NC
22
COM
23
NO
31
NC
32
COM
33
NO
XD24
5
+24 VD +24 V DC 200 mA
6
DICOM Digital input ground
7
+24 VD +24 V DC 200 mA
8
DIOGND Digital input/output ground
XDIO
1
DIO1 MCB trip command (internally used)
2
DIO2 MCB status closed (internally used)
XDI
1
DI1 Stop (0) / Start (1)
2
DI2 Forward (0) / Reverse (1)
3
DI3 Reset
4
DI4 Acc/Dec time set 1 (0) / set 2 (1)
5
DI5 Constant speed 1 (1 = On)
6
DI6 By default, not in use
X13
X205
XETH
24 VDC, 2 A (internally used)
Speed reference
0
(
2
)
…10 V
,
R
in
>200 kohm
By default not in use.
0(4)20 mA, R
in
>100 ohm
Fault
Ready
250 VAC/ 30 VDC
2 A
Running
250 VAC/ 30 VDC
2 A
Fault (-1)
250 VAC/ 30 VDC
2 A
Digital interlock
Digital input/outputs
Digital inputs
Analog outputs
Motor speed rpm
0…20 mA
,
R
L
<500 ohm
Motor current
0…20 mA, RL<500 ohm
XRO1, XRO2, XRO3
Relay outputs
Control panel connection (internally used)
Memory unit connection (internally used)
PC ethernet connection for Drive Composer
Default control connections for the factory macro