Control system and interfaces 47
Customer interface terminal block
Customer Interface Terminal Block
X1
Customer Interface Terminal Block
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
41
43
45
47
53
55
57
59
61
62
63
64
65
66
67
RO, NC/NO can be selective, 250 V AC/24 V DC,2A
Emergency off reset
to be check
24Vdc 24Vdc for digit input
MCB close cmd
MCB open cmd
MCB trip/unlock cmd 1
MCB closed status
MCB open status
MCB ready status
Emergency off 1
Emergency off 2
Remote MCB close cmd
Remote MCB open cmd
Alarm
floating contacts to customer
making capability: 40 A
thermal current: Ith = 6 A @40°C
breaking capability:
AC-15 50 Hz Ie(240 V)=4 A, Ie(500 V)=2 A
DC-13 Ie(24 V)=2.5 A, Ie(110 V)=0.7 A, Ie(240 V)=0.4 A
minimum load: 17 V, 5 mA
isolation rated voltage 690 V AC
Connect contact from customer
internal supply 24 Vdc, 5mA
Connect contact from customer
internal supply 24 Vdc, 5 mA, max resistance 140
Connect contact from customer
internal supply 24 Vdc, 5mA
Connect contacts from customer
Max resistance 60
.
Internal supply, 24 Vdc, 25 mA
Connect contacts from customer
internal supply 24Vdc, 5 mA
Switchable