Installation checklist 87
Electrical installation
Door interlocking
Main circuit breaker (MCB)
10. Visual inspection:
no badly affixed or damaged components
no foreign objects inside cabinet
no dirt, dust and humidity inside cabinet
1. Types and cross-sections of control cables suitable for the signal type and signal level
2. Types and cross-sections of power cables selected according to the ACS580MV Engineering
Guideline
3. Pulse encoder cable screens connected to screen grounding point and not connected directly
to the pulse encoder interface (only applicable for drives with pulse encoder interface)
4. Internal cabling to integrated transformer (power, auxiliary, control and heater cables) made
according to the instructions in this manual (Chapter
Electrical installation)
5.
Cable entry made according to the instructions in this manual (Chapter
Electrical installation)
6. All control cable screens and conductors are connected according to the instructions in this
manual (Chapter
Electrical installation), appropriately labeled, and the customer-side
connections are completed
7.
Heating cable (if supplied) installed according to the instructions in this manual (Chapter
Electrical installation)
8. Ground cable of drive securely connected at both ends
9. Input and motor cables not connected at both ends (cables must be meggered before
connection, drive optional - recommended in case of long storage time, humid environment or
visible transportation damages)
1. Door locks tested and in operation
2. The manual release of the door safety switch(es) is in the locked position.
1. Type of MCB selected as per ACS580MV Engineering Guideline