Technical data
90
Mains cable fuses
Fuses for short-circuit protection of the mains cable are listed below. The fuses also
protect the adjoining equipment of the drive in case of a short-circuit. Check that the
operating time of the fuse is below 0.5 seconds. The operating time depends on
the supply network impedance and the cross-sectional area, material and length of
the supply cable. See also Planning the electrical installation: Thermal overload and
short-circuit protection. For UL recognized fuses, see US tables.
Note 1: In multicable installations, install only one fuse per phase (not one fuse per conductor).
Note 2: Larger fuses must not be used.
Note 3: Fuses from other manufacturers can be used if they meet the ratings.
Standard gG fuses
ACS800-02
size
Input
current
Fuse
AAA
2
s V Manufacturer Type IEC size
Three-phase supply voltage 208 V, 220 V, 230 V or 240 V
-0080-2 201 250 550 000 500 ABB Control OFAF1H250 1
-0100-2 239 315 1 100 000 500 ABB Control OFAF2H315 2
-0120-2 285 315 1 100 000 500 ABB Control OFAF2H315 2
-0140-2 391 500 2 900 000 500 ABB Control OFAF3H500 3
-0170-2 428 500 2 900 000 500 ABB Control OFAF3H500 3
-0210-2 506 630 4 000 000 500 ABB Control OFAF3H630 3
-0230-2 599 630 4 000 000 500 ABB Control OFAF3H630 3
-0260-2 677 800 7 400 000 500 ABB Control OFAF3H800 3
-0300-2 707 800 7 400 000 500 ABB Control OFAF3H800 3
Three-phase supply voltage 380 V, 400 V or 415 V
-0140-3 196 250 550 000 500 ABB Control OFAF1H250 1
-0170-3 237 315 1 100 000 500 ABB Control OFAF2H315 2
-0210-3 286 315 1 100 000 500 ABB Control OFAF2H315 2
-0260-3 438 500 2 900 000 500 ABB Control OFAF3H500 3
-0320-3 501 630 4 000 000 500 ABB Control OFAF3H630 3
-0400-3 581 630 4 000 000 500 ABB Control OFAF3H630 3
-0440-3 674 800 7 400 000 500 ABB Control OFAF3H800 3
-0490-3 705 800 7 400 000 500 ABB Control OFAF3H800 3
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0170-5 191 250 550 000 500 ABB Control OFAF1H250 1
-0210-5 243 315 1 100 000 500 ABB Control OFAF2H315 2
-0260-5 291 315 1 100 000 500 ABB Control OFAF2H315 2
-0320-5 424 500 2 900 000 500 ABB Control OFAF3H500 3
-0400-5 498 630 4 000 000 500 ABB Control OFAF3H630 3
-0440-5 543 630 4 000 000 500 ABB Control OFAF3H630 3
-0490-5 590 630 4 000 000 500 ABB Control OFAF3H630 3
-0550-5 669 800 7 400 000 500 ABB Control OFAF3H800 3
-0610-5 702 800 7 400 000 500 ABB Control OFAF3H800 3
PDM code: 00096931-G