EasyManua.ls Logo

ABB ACS800-04M - Page 108

ABB ACS800-04M
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
108 Technical data
-0170-7 156 1520 350 68 500 690 Bussmann 170M3818D DIN1*
-0210-7 191 1610 400 74 000 690 Bussmann 170M5808D DIN2*
-0260-7 217 1610 400 74 000 690 Bussmann 170M5808D DIN2*
-0320-7 298 3010 630 275 000 690 Bussmann 170M5812D DIN2*
-0400-7 333 2650 630 210 000 690 Bussmann 170M6810D DIN3
-0440-7 377 4000 800 465 000 690 Bussmann 170M6812D DIN3
-0490-7 423 4790 900 670 000 690 Bussmann 170M6813D DIN3
-0550-7 468 4790 900 670 000 690 Bussmann 170M6813D DIN3
-0610-7 533 5550 1000 945 000 690 Bussmann 170M6814D DIN3
A
2
s value for -7 units at 660 V
1)
minimum short-circuit current of the installation
Note 1: See
Thermal overload and short-circuit protection
(page 46). For UL recognized fuses, see
NEMA data
(page 114).
Note 2: In multi-cable installations, install only one fuse per phase (not one fuse per conductor).
Note 3: Larger fuses than the recommended ones must not be used.
Note 4: Fuses from other manufacturers can be used if they meet the ratings and the melting curve of the fuse
does not exceed the melting curve of the fuse mentioned in the table.
0009693, 00556489
Ultrarapid (aR) fuses
ACS800-
04 size
Input
current
A
Min.
short-
circuit
current
1)
Fuse
AA
A
2
s
V Manufacturer Type DIN 43620 Size

Table of Contents

Other manuals for ABB ACS800-04M