Operation principle and hardware description 27
Type code
The type code contains information on the specifications and configuration of the
drive. The first digits from left express the basic configuration (for example,
ACS800-04-0170-5). The optional selections are given thereafter, separated by plus
signs (for example, +E202). The main selections are described below. Not all
selections are available for all types. For more information, refer to
ACS800 Ordering
Information
(3AFY64556568, available on request).
Type code for ACS800-04 and ACS800-U4 pre-assembled units
Selection Alternatives
Product series ACS800 product series
Type 04 Drive module. When no options are selected: 6-pulse diode input
bridge, IP00, top entry of cables, side exit, RDCU drive control unit,
no control panel, no EMC filter, Standard Control Program, pedestal
with output on the long side, output busbar set for motor, base and
wall mounting brackets, one set of manuals. Pre-assembled unit.
U4 Drive module (USA). When no options are selected: 6-pulse diode
bridge, UL open type, open chassis, top entry of cables, side exit, no
control panel, no EMC filter, US version of the Standard Control
Program (three-wire start/stop as default setting), common mode
filter in frame size R8, pedestal with output on the long side, output
busbar set for motor, base and wall mounting brackets, one set of
manuals.
Size Refer to
IEC data
(page 99) or
NEMA data
(page 114).
Voltage range
(nominal rating in bold)
2 208/220/230/240 VAC
3380/400/415 VAC
5 380/400/415/440/460/480/500 VAC
7525/575/600/690 VAC
Option codes (+ codes)
Resistor braking D150 brake chopper and busbars for brake resistor and DC connection
Filter E210 EMC/RFI filter for second environment TN/IT
(grounded/ungrounded) system
E208 common mode filter
Pedestal and output
busbars
0H35
4
no pedestal
Control panel J400 CDP 312R control panel including a 3-metre panel connection cable
J410 RPMP-11 control panel mounting platform kit including a 3-metre
panel connection cable but no control panel
J413 RPMP-21 control panel holder
Fieldbus K... Refer to
ACS800 Ordering Information
(3AFY64556568).
I/O L...
Control program N...
Language of manual R...
Specialties P901 coated boards
P904 extended warranty
Safety features Q950 Prevention of unexpected start-up (not to be used with +Q967),
including 500 mm (19.68 in.) cable outside the drive module in frame
size R7, 600 mm (23.62 in.) cable outside the drive module in frame
size R8.
Q967 Safe torque off (STO) (not to be used with +Q950), including
500 mm (19.68 in.) cable outside the drive module in frame size R7,
600 mm (23.62 in.) cable outside the drive module in frame size R8.