80 Motor control and I/O board (RMIO)
Relay outputs
Three programmable relay outputs
Switching capacity 8 A at 24 V DC or 250 VAC, 0.4 A at 120 V DC
Minimum continuous current 5 mA rms at 24 V DC
Maximum continuous current 2 A rms
Insulation test voltage 4 kV AC, 1 minute
DDCS fiber-optic link
With optional communication adapter module RDCO. Protocol: DDCS
(ABB Distributed Drives Communication System)
24 V DC power input
Voltage 24 V DC ± 10%
Typical current consumption
(without optional modules)
250 mA
Maximum current consumption 1200 mA (with optional modules inserted)
The terminals on the RMIO board as well as on the optional modules attachable to the board fulfill the
Protective Extra Low Voltage (PELV) requirements stated in EN 50178 provided that the external
circuits connected to the terminals also fulfill the requirements and the installation site is below
2000 m (6562 ft). Above 2000 m (6562 ft), see page 61
.