Installation checklist and start-up
107
Installation checklist and start-up
What this chapter contains
This chapter contains an installation checklist, a start-up procedure for the drive, and
listings of parameters specific to the ACS800-17.
Installation checklist
Check the mechanical and electrical installation of the drive before start-up. Go
through the checklist below together with another person.
WARNING! Only qualified electricians are allowed to commission the drive. Read
and follow the Safety instructions on the first pages of this manual. Neglecting the
safety instructions can cause injury or death.
Check…
MECHANICAL INSTALLATION
The ambient operating conditions are allowed. See Electrical installation, Technical data: IEC ratings or Ambient
conditions.
The unit is fixed properly to floor. See Mechanical installation.
The cooling air will flow freely.
ELECTRICAL INSTALLATION See Planning the electrical installation, Electrical installation.
The motor and the driven equipment are ready for start.
The EMC filter (option +E202) is disconnected if the drive is connected to an IT (ungrounded) system.
The drive is grounded properly.
The supply (input power) voltage matches the nominal input voltage of the drive.
The supply (input power) connection to the input terminals are OK and the phase order is correct.
Appropriate supply (input power) fuses and disconnector are installed.
The motor connections at the output terminals are OK.
The motor cable is routed away from other cables.
Settings of the auxiliary voltage transformer.
There are no power factor compensation capacitors in the motor cable.
The external control connections inside the drive are OK.
There are no tools, foreign objects or dust from drilling inside the drive.
Supply (input power) voltage cannot be applied to the output of the drive (with a bypass connection).