Installation checklist and start-up
112
Default values of parameters with the ACS800-17
When the IGBT Supply Control Program is loaded into the ACS800-17, the following
parameters receive the default values given in the table below. Do not change the
default values. If they are changed, the drive will not operate properly.
31.02 TRIAL TIME Defines the time for the automatic fault reset function. See parameter
31.01.
R 30 s
1.0 … 180.0 s Allowed resetting time 100 …
18000
31.03 DELAY TIME Defines the time that the drive will wait after a fault before attempting
an automatic reset. See parameter 31.01.
R0 s
0.0 … 3.0 s Resetting delay 0 … 300
31.04 OVERCURRENT Activates/deactivates the automatic reset for the line converter
overcurrent fault.
BNO
NO Inactive 0
YES Active 65535
31.05 OVERVOLTAGE Activates/deactivates the automatic reset for the intermediate link
overvoltage fault.
BNO
NO Inactive 0
YES Active 65535
31.06 UNDERVOLTAGE Activates/deactivates the automatic reset for the intermediate link
undervoltage fault.
BNO
NO Inactive 0
YES Active 65535
Parameter Default value
11.01 DC REF SELECT FIELDBUS
11.02 Q REF SELECT PARAM 24.02
70.01 CH0 NODE ADDR 120
70.19 DDCS CH0 HW CONN RING
70.20 CH3 HW CONNECTION RING
71.01 CH0 DRIVEBUS MODE NO
98.01 COMMAND SEL MCW
98.02 COMM. MODULE INU COM LIM
No. Name/Value Description T./FbEq Def.