Planning the electrical installation
79
A diagram of the cable routing is below.
Control cable ducts
90 °
min 500 mm (20 in.)
Motor cable
Input power cable
Control cables
min 200 mm (8 in.)
min 300 mm (12 in.)
Motor cable
Power cable
Drive
230/120 V24 V24 V 230/120 V
Lead 24 V and 230/120 V control
cables in separate ducts into the
inside of the cabinet.
Not allowed unless the 24 V cable is
insulated for 230 V (120 V) or
insulated with an insulation sleeving
for 230 V (120 V).