Technical data
156
Terminal and lead-through data for the motor cable
Units without common motor terminal cubicle (no option +H359)
When the drive is not equipped with common motor terminal cubicle, the motor
cables enter the inverter module cubicle(s).
Inverter unit
configuration
No. of busbars Screw size
Tightening
torque
Cable lead-
throughs
R7i, n×R8i n×3 M12 (½”) 70 N·m (52 lbf·ft)
n × [6 × Ø60 mm
(2.36“)]
Dimensions of output busbar in
inverter module cubicle
n = number of inverter modules