Actual signals and parameters
115
63.21 LINEAR FRIC @ 80% See 63.18 INEAR FRIC @ 20%.
-1000.0…1000.0 Nm
-1000.0…1000.0 lbft
Setting range. 10 = 1 Nm
10 = 1 lbft
63.22 LINEAR FRIC @ MAX See 63.18 INEAR FRIC @ 20%.
-1000.0…1000.0 Nm
-1000.0…1000.0 lbft
Setting range. 10 = 1 Nm
10 = 1 lbft
63.23 WEB 2 SELECT Sets or selects the activation signal source for switching the gain and
integration time for the tension PI regulator.
NOT SEL Not selected. P-GAIN 1 and INTEG TIME 1 are used (63.0163.03). 1
DI2 Digital input DI2 = 1 selects P-GAIN 2 and INTEG TIME 2
(63.2463.26).
2
DI3 See selection DI2. 3
DI4 See selection DI2. 4
DI5 See selection DI2. 5
DI6 See selection DI2. 6
DI7 See selection DI2. 7
DI8 See selection DI2. 8
DI9 See selection DI2. 9
DI10 See selection DI2. 10
DI11 See selection DI2. 11
DI12 See selection DI2. 12
FIELDBUS See selection DI2. Instead of a digital input, the command comes from
06.03 DATASET 1 WORD 3 bit 01. See chapter Fieldbus control.
13
63.24 P-GAIN 2 MIN Optional minimum proportional gain of the tension PI regulator.
0.01…1000.00 K Setting range. 100 = 1 K
63.25 P-GAIN 2 MAX Optional maximum proportional gain of the tension PI regulator.
P-GAIN 2 MIN…1000.00 K Setting range. 100 = 1 K
63.26 INTEG TIME 2 Optional integration time of the tension PI regulator.
10…10000 ms Setting range. 1 = 1 ms
63.27 STALL ENABLE If “NORMAL GAIN” is selected, stall mode is active when the line
speed is less than 63.29 STALL SPEED. When stall mode is active,
03.08 TENSION REF is reduced to a percentage of 03.07 TENSION
SETPOINT as defined by 63.28 STALL SETPNT. In this mode, the PI
regulator uses the normal gain and integration time.
If “STALL GAIN” is selected, the reaction is the same as “NORMAL
GAIN” except that the PI regulator uses 63.30 STALL P-GAIN and
63.31 STALL INTEG.
DISABLE Stall function is not selected. 1
NORMAL GAIN Stall function is selected and PI regulator gain at stall equals P-GAIN. 2
STALL GAIN Stall function is selected and PI regulator gain at stall equals 63.30
STALL P-GAIN.
3
63.28 STALL SETPOINT
1…100% Setting range. 1 = 1%
63.29 STALL SPEED Percentage of 11.05 EXT1 REF MAXIMUM. Goes into stall mode
below this speed.