Program features
28
Programmable analog outputs
Two programmable current outputs are available as standard, and two outputs can
be added by using an optional Analog I/O Extension Module. Analog output signals
can be inverted and filtered.
The analog output signals can be proportional to motor speed, process speed
(scaled motor speed), output frequency, output current, motor torque, motor power,
etc.
It is possible to write a value to an analog output through a serial communication
link.
Update cycles in the Control Program
Settings
Diagnostics
Output Cycle
AO / standard 50 ms
AO / extension 50 ms
Parameter Additional Information
Group 15 ANALOG OUTPUTS Value selection and processing (standard outputs)
Group 35 MTR TEMP MEAS Motor temperature measurement
Group 98 OPTION MODULES Activation of optional I/O
Actual Value Additional Information
01.22, 01.23 Values of the standard outputs
01.28, 01.29 Values of the optional outputs
Warning
IO CONF Improper use of optional I/O