216 Parameters
51
51 FBA settings
Fieldbus adapter-specific settings.
51.01 FBA type Displays the type of the connected fieldbus adapter module.
0 = Fieldbus module is not found, or it is not properly
connected, or parameter 50.01 Fba enable is set to Disable,
1 = FPBA-xx PROFIBUS-DP adapter module, 32 = FCAN-xx
CANopen adapter module, 37 = FDNA-xx DeviceNet adapter
module
51.02 FBA par2 Parameters 51.0251.26 are adapter module-specific. For
more information, see the User’s Manual of the fieldbus
adapter module. Note that not all of these parameters are
necessarily visible.
-
……
51.26 FBA par26 See parameter 51.02 FBA par2.-
51.27 FBA par refresh Validates any changed adapter module configuration
parameter settings. After refreshing, the value reverts
automatically to Done.
Note: This parameter cannot be changed while the drive is
running.
Done Refreshing done. 0
Refresh Refreshing. 1
51.28 Par table ver Displays the parameter table revision of the fieldbus adapter
module mapping file stored in the memory of the drive.
In format xyz, where x = major revision number; y = minor
revision number; z = correction number.
0x0000 … 0xFFFF Parameter table revision. 1 = 1
51.29 Drive type code Displays the drive type code of the fieldbus adapter module
mapping file stored in the memory of the drive.
0 … 65535 Drive type code of fieldbus adapter module mapping file. 1 = 1
51.30 Mapping file ver Displays the fieldbus adapter module mapping file revision
stored in the memory of the drive in decimal format. Example:
1 = revision 1.
0 … 65535 Mapping file revision. 1 = 1
51.31 D2FBA comm sta Displays the status of the fieldbus adapter module
communication.
Idle Adapter is not configured. 0
Exec.init Adapter is initializing. 1
Time out A timeout has occurred in the communication between the
adapter and the drive.
2
Conf.err Adapter configuration error: The major or minor revision code
of the common program revision in the fieldbus adapter
module is not the revision required by the module (see
parameter 51.32 FBA comm sw ver) or mapping file upload
has failed more than three times.
3
Off-line Adapter is off-line. 4
On-line Adapter is on-line. 5
Reset Adapter is performing a hardware reset. 6
No. Name/Value Description FbEq