ABB moulded case circuit breaker (Tmax)ABB miniature circuit
breaker
FrameACS880-
01-…
kA
1)
TypekA
1)
Type
--10S 803 S-B/C 13R107A6-5
--10S 803 S-B/C 20R111A0-5
--10S 803 S-B/C 25R2014A-5
--10S 803 S-B/C 32R2021A-5
--10S 803 S-B/C 50R3027A-5
--10S 803 S-B/C 63R3034A-5
--10S 803 S-B/C 63R4040A-5
--10S 803 S-B/C 75R4052A-5
65XT2 L 160 Ekip LS/I In=160 3p F F10S 803 S-B/C 125R5065A-5
65XT2 L 160 Ekip LS/I In=160 3p F F10S 803 S-B/C 125R5077A-5
65XT4 L 250 Ekip LS/I In=250 3p F F--R6096A-5
65XT4 L 250 Ekip LS/I In=250 3p F F--R6124A-5
65XT4 L 250 Ekip LS/I In=250 3p F F--R7156A-5
65T4 L 320 PR221DS-LS/I In=320 3p F F--R7180A-5
65T5 L 630 PR221DS-LS/I In=630 3p F F--R8240A-5
65T5 L 630 PR221DS-LS/I In=630 3p F F--R8260A-5
65T5 L 630 PR221DS-LS/I In=630 3p F F--R9302A-5
65T5 L 630 PR221DS-LS/I In=630 3p F F--R9361A-5
65T5 L 630 PR221DS-LS/I In=630 3p F F--R9414A-5
U
n
= 690 V
18XT2 L 160 Ekip LS/I In=160 3p F F10S 803 S-B/C 13R307A4-7
18XT2 L 160 Ekip LS/I In=160 3p F F10S 803 S-B/C 20R309A9-7
18XT2 L 160 Ekip LS/I In=160 3p F F10S 803 S-B/C 25R314A3-7
18XT2 L 160 Ekip LS/I In=63 3p F F10S 803 S-B/C 32R3019A-7
18XT2 L 160 Ekip LS/I In=63 3p F F10S 803 S-B/C 50R3023A-7
18XT2 L 160 Ekip LS/I In=63 3p F F10S 803 S-B/C 63R3027A-7
18XT2 L 160 Ekip LS/I In=63 3p F F10S 803 S-B/C 63R5035A-7
18XT2 L 160 Ekip LS/I In=100 3p F F10S 803 S-B/C 80R5042A-7
18XT2 L 160 Ekip LS/I In=100 3p F F10S 803 S-B/C 80R5049A-7
20XT2 L 160 Ekip LS/I In=160 3p F F10S 803 S-B/C 125R6061A-7
20XT2 L 160 Ekip LS/I In=160 3p F F10S 803 S-B/C 125R6084A-7
20XT4 L 250 Ekip LS/I In=250 3p F F--R7098A-7
20XT4 L 250 Ekip LS/I In=250 3p F F--R7119A-7
20XT4 L 250 Ekip LS/I In=250 3p F F--R8142A-7
35T4 L 320 PR221DS-LS/I In=320 3p F F--R8174A-7
35T5 L 400 PR221DS-LS/I In=400 3p F F--R9210A-7
35T5 L 630 PR221DS-LS/I In=630 3p F F--R9271A-7
1)
Maximum allowed rated conditional short-circuit current (IEC 61800-5-1) of the electrical power
network