Note: Note: Do not install a drive with the EMC filter +E202 connected to a system that
the filter is not suitable for. This can cause danger, or damage the drive.
Note: Do not install a drive with the ground-to-phase varistor connected to a system
that the varistor is not suitable for. If you do, the varistor circuit can be damaged.
If you install the drive to any other system than symmetrically grounded TN-S system,
you may need to disconnect the EMC filter or the ground-to-phase varistor. See ACS880
frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions
(3AUA0000125152 [English])
■ Category C3
The drive complies with the standard with the following provisions:
• The drive is equipped with EMC filter +E200.
• The motor and control cables are selected as specified in this manual.
• The drive is installed according to the instructions given in this manual.
•
For the maximum motor cable length, see section Motor connection data.
WARNING! drive of category C3 is not intended to be used on a low-voltage
public network which supplies domestic premises. Radio frequency interference
is expected if the drive is used on such a network.
Note: Note: Do not install a drive with the EMC filter +E200 connected to a system that
the filter is not suitable for. This can cause danger, or damage the drive.
Note: Do not install a drive with the ground-to-phase varistor connected to a system
that the varistor is not suitable for. If you do, the varistor circuit can be damaged.
If you install the drive to any other system than symmetrically grounded TN-S system,
you may need to disconnect the EMC filter or the ground-to-phase varistor. See ACS880
frames R1 to R11 EMC filter and ground-to-phase varistor disconnecting instructions
(3AUA0000125152 [English])
■ Category C4
The drive complies with the C4 category with these provisions:
1. It is ensured that no excessive emission is propagated to neighboring low-voltage
networks. In some cases, the natural suppression in transformers and cables is
sufficient. If in doubt, the supply transformer with static screening between the
primary and secondary windings can be used.
Technical data 239