DescriptionTermConnection
XDI Digital inputs
Stop (0) / Start (1)DI1
1
DI1
DI2
DI3
DI4
DI5
DI6
2
3
4
5
6
+24VD
DIOGND
2
5
XD24
Forward (0) / Reverse (1)DI2
ResetDI3
Acc/Dec time selectDI4
Constant speed 1 (1 = On)DI5
By default, not in use.DI6
Safe torque off circuits must be closed for the
drive to start.
OUT
1
OUT
2
SGND
3 IN1
4 IN2
SGND
IN1
IN2
Safety options connectionX12
Control panel connectionX13
Memory unit connectionX205
The wire size accepted by all screw connectors (for both stranded and solid wire) is
0.5 2.5 mm
2
(24…12 AWG). The torque is 0.5 N·m (5 lbf·in).
Start-up the drive
Before you start up the drive, make sure that the installation is completed.
Make sure also that it is safe to start the motor. Disconnect the motor from
other machinery if there is a risk of damage or injury.
Before you activate the automatic fault reset or automatic restart functions
of the drive control program, make sure that no dangerous situations can
occur. These functions reset the drive automatically and continue operation
after a fault or supply break. If these functions are activated, the installation
must be clearly marked as defined in IEC/EN/UL 61800-5-1, subclause 6.5.3,
for example, "THIS MACHINE STARTS AUTOMATICALLY".
Use the control panel to do the start-up procedure. The two commands at the bottom
of the display show the functions of the two softkeys and located below the
display. The commands assigned to the softkeys are different depending on the
context. Use the arrow keys , , and to move the cursor or change values
depending on the active view. Key
?
shows a context-sensitive help page.