Start-up 149
Setting up the parameters, and performing the first start
Supply modules:
Set the correct voltage range, supply unit parameter 195.01 Supply voltage.
•Su
pply modules with option +C188 (direct-on-line cooling fan): Set bit 13 of 195.20 HW options
word 1.
If your supply unit consists of more than one module, parameters 195.30 Parallel type filter and
195.31 Parallel connection rating id need to be set. First, select the correct voltage range with
parameter 195.30 Parallel type filter. Then, select the correct supply unit type with parameter
195.31 Parallel connection rating id.
Inverter modules:
•Inverter modules with option +C188 (direct-on-line cooling fan): Set bit 14 of 95.20 HW options
word 1.
With parallel-connected R8i modules, select the inverter unit type in parameter 95.31 Parallel
connection rating id. You can filter the list using parameter 95.30.
If the drive is powered from external power supplies, some parameter adjustments need to be
made (eg, inverter unit parameter 95.04 Control board supply). See the inverter unit firmware
manual.
Check that inverter unit parameter 95.09 Fuse switch control is set to Disable.
Setup the drive control program, and perform the first start of the drive and motor. See the
appropriate start-up guide, or firmware manual. There is a separate start-up guide only for some
control programs.
Set up the communication between inverter unit and supply unit. Connect the fiber optic cable
between CH 0 (RDCO module) in supply unit and CH1 (RDCO module) in inverter unit. The
communication also requires setting of inverter unit parameter 95.20 HW options word 1, and
supply unit parameter 195.20 HW options word 1. See the firmware manuals.
For commissioning both supply unit and inverter unit with a single control panel, a panel bus
configuration (via FDPI-02) is needed.
Set up the panel bus: For the inverter unit, check and select (if needed) node 1 with the
parameter 49.01 Node ID number. For the supply unit, check and select (if needed) node 2 with
the parameter 149.01 Node ID. Note: The new settings take effect only after refreshing the
parameter settings with inverter unit parameter 49.06 Refresh settings and supply unit parameter
149.06 Refresh settings.
If you need more information on the use of the control panel, see ACX-AP-x assistant control panels
user's manual (3AUA0000085685 [English]).
Stop the motor and drive.
Drives with a fieldbus adapter module (if applicable): Set the fieldbus parameters. Activate the
appropriate assistant in the control program, or see the user’s manual of the fieldbus adapter
module, and the drive firmware manual. Not all control programs include assistants.
Check that the communication works between the drive and the PLC.
Drives with an encoder interface module
(if applicable): Set the encoder parameters. Activate the
appropriate assistant in the control program, or see the user’s manual of the encoder interface
module, and the drive firmware manual. Not all control programs include assistants.