Deratings with selection High speed mode of parameter 95.15 Special HW settingsACS880-
07-…
Maximum output frequency120 Hz output frequency
Heavy-
duty
use
Light-
duty
use
Nominal useHeavy-
duty
use
Light-
duty
use
Nominal use
I
Hd
I
Ld
P
n
I
n
f
max
I
Hd
I
Ld
P
n
I
n
f
AAkWAHzAAkWAHz
68797583500981131101191200119A-7
727975835001191351321421200142A-7
839190965001421651601741200174A-7
8396901015001742002002101200210A-7
1011241101305002102572002711200271A-7
1572222002323752553203153301200330A-7
2002502502603753253603553701200370A-7
236****280250290375360****4204004301200430A-7
2382612502703754154554504701200470A-7
2622902503003754555055005221200522A-7
3003303153403755055715605901200590A-7
350****430400450375571****6306306501200650A-7
350****430400450375571****7057107211200721A-7
The ratings apply at an ambient temperature of 40 °C (104 °F).
3AXD00000588487
Output frequency
f
Maximum output frequency with High speed mode
f
max
Nominal voltage of the drive
U
n
Continuous rms output current. No overload capability at 40 °C (104 °F)
I
n
Typical motor power in no-overload use.
P
n
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
I
Ld
Typical motor power for light-overload use.
P
Ld
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
I
Hd
* Continuous rms output current allowing 30% overload for 1 minute every 5 minutes
** Continuous rms output current allowing 25% overload for 1 minute every 5 minutes
*** Continuous rms output current allowing 40% overload for 1 minute every 5 minutes
**** Continuous rms output current allowing 44% overload for 1 minute every 5 minutes
***** Continuous rms output current allowing 45% overload for 1 minute every 5 minutes
206 Technical data