Example brake resistor(s)Internal brake chopperACS880-
07-…
P
Rcont
E
R
RTypeR
min
P
brcont
kWkJohmohmkW
624006.0SAFUR80F5005.4550096A-5
624006.0SAFUR80F5005.4750124A-5
936004.0SAFUR125F5003.3900156A-5
936004.0SAFUR125F5003.31100180A-5
13.554002.7SAFUR200F5002.31320240A-5
13.554002.7SAFUR200F5002.31320260A-5
13.554002.7SAFUR200F5002.31600302A-5
13.554002.7SAFUR200F5002.31600361A-5
13.554002.7SAFUR200F5002.31600414A-5
1872002.002×SAFUR125F5002.02500460A-5
1872002.002×SAFUR125F5002.02500503A-5
27108001.352×SAFUR200F5001.33150583A-5
27108001.352×SAFUR200F5001.33150635A-5
40162000.903×SAFUR200F5000.74000715A-5
40162000.903×SAFUR200F5000.74000820A-5
U
n
= 690 V
243513.0SACE15RE1313550061A-7
243513.0SACE15RE1313650084A-7
4.518008.0SAFUR90F5758900098A-7
4.518008.0SAFUR90F57581100119A-7
624006.0SAFUR80F50061320142A-7
624006.0SAFUR80F50061600174A-7
936004.0SAFUR125F50042000210A-7
936004.0SAFUR125F50042000271A-7
1336002.7SAFUR200F5002.22850330A-7
1336002.7SAFUR200F5002.22850370A-7
1336003SAFUR200F50022850430A-7
18720022xSAFUR125F50023500425A-7
18720022xSAFUR125F50023500470A-7
18720022xSAFUR125F50023500522A-7
18720022xSAFUR125F50024000590A-7
18720022xSAFUR125F5001.84000650A-7
18720022xSAFUR125F5001.84000721A-7
3AXD10000044776
Maximum continuous braking power. The braking is considered continuous if the braking time exceeds
30 seconds.
P
brcont
The minimum allowed resistance value of the brake resistor
R
min
Resistance value for the listed resistor assembly
R
Short energy pulse that the resistor assembly withstands every 400 seconds
E
R
Resistor braking 267