1.
Stop the drive and do the steps in section Electrical safety precautions (page 15)
before you start the work.
2. Remove the front cover(s) if not already removed.
3. Frame R3: Pull the control panel holder up.
4. Attach the cable conduits to the conduit plate. Make sure the conduit is correctly
bonded at both ends and that conductivity is consistent throughout the conduit. Slide
the control cables through the conduit. Cut to suitable length (note the extra length
of the grounding conductors) and strip the conductors.
5. Ground the outer shields of all control cables 360 degrees at a grounding clamp.
6. Route the cables as shown below.
7. Secure the cables inside the drive mechanically.
8. Frame R3: Ground the pair cable shields and grounding wires under the grounding
clamp screw at the cable entry.