UL (NEC) RATINGS
Output ratingsMax.
current
Input
current
Frame
size
ACS880-11-
Heavy-duty useLight-duty useApp.
power
P
Hd
I
Hd
P
Ld
I
Ld
S
n
I
max
I
1
hpAhpAkVAAA
10.014.015.021.01826.315.6R3021A-5
15.021.020.027.02335.721.3R6
027A-5
1)
20.027.025.034.02945.926.2R6034A-5
1)
25.034.030.040.03557.831.2R6040A-5
1)
30.040.040.052.04568.040.1R6052A-5
40.052.050.065.05688.449.5R6065A-5
1)
50.065.060.077.067110.560.2R6077A-5
1)
60.077.075.096.08714874R8101A-5
75.096.0100.0124.0107178100R8124A-5
100.0124.0125.0156.0137247120R8156A-5
125.0156.0150.0180.0156287147R8180A-5
3AXD00000588487
1)
These ratings are not to be used for drives with degree of protection of IP55 (UL Type 12) option +B056.
Nominal voltage of the drive
U
n
Nominal input current (rms) at 40 °C (104 °F)
I
1
Maximum output current. Available for 10 seconds at start, otherwise as long as allowed
by drive temperature. 140% 200% of I
Hd
, depending on power rating.
I
max
Continuous rms output current. No overload capability at 40 °C (104 °F). This is indicated
in the type designation label as output current I
2
.
I
2
Typical motor power in no-overload use
P
n
Apparent power (no overload)S
n
Continuous rms output current allowing 10% overload for 1 minute every 5 minutes
I
Ld
Typical motor power for light-overload use
P
Ld
Continuous rms output current allowing 50% overload for 1 minute every 5 minutes
I
Hd
Typical motor power for heavy-duty use
P
Hd
Note: To achieve the rated motor power given in the table, the rated current of the drive must be
higher than or equal to the rated motor current. The power ratings apply to most IEC 34 motors
at the nominal voltage of the drive.
ABB recommends to select the drive, motor and gear combination for the required motion profile
with the DriveSize dimensioning tool available from ABB.