■ gG fuses DIN 43620 blade style
gG fuses can be used for frames R3 and R6 if they operate rapidly enough (max. 0.1
seconds). ABB recommends, however, aR fuses. gG fuses are not allowed for frame
R8.
gG fuses (one fuse per phase)Input cur-
rent
Min.
short-cir-
cuit cur-
rent1)
ACS880-
11-…
Size DIN
43620
ABB typeVoltage
rating
I2tNominal
current
VA2sAAA
3-phase U
n
= 400 V
000OFAF000H16500700168.012009A4-3
000OFAF000H165007001610.012012A6-3
000OFAF000H2550025002514.0200017A-3
000OFAF000H3250045003220.0250025A-3
000OFAF000H4050077004027.0350032A-3
000OFAF000H50500154005033.0400038A-3
000OFAF000H63500213006340.0500045A-3
000OFAF000H80500370008051.0800061A-3
000OFAF000H1005006360010063.01000072A-3
000OFAF000H1005006360010076.01000087A-3
3-phase U
n
= 500 V
000OFAF000H16500700165.812007A6-5
000OFAF000H16500700167.812011A0-5
000OFAF000H2550025002510.6200014A-5
000OFAF000H3250045003215.6250021A-5
000OFAF000H4050077004021.3350027A-5
000OFAF000H50500154005026.2400034A-5
000OFAF000H63500213006331.2500040A-5
000OFAF000H80500370008040.1800052A-5
000OFAF000H1005006360010049.51000065A-5
000OFAF000H1005006360010060.21000077A-5
1)
Minimum short-circuit current of the installation
■ Quick guide for selecting between gG and aR fuses
The combinations (cable size, cable length, transformer size and fuse type) in this table
fulfill the minimum requirements for the correct operation of the fuse. Use this table to
select between gG and aR fuses or calculate the short-circuit current of the installation
as described in section Calculating the short-circuit current of the installation (page 174).
Technical data 173