EasyManua.ls Logo

ABB ACS880-11 - Definitions; Derating

ABB ACS880-11
232 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NoiseHeat dissipationP
n
I
2
Sine filter typeType
ACS880-11
TotalFilterDrive
dB(A)WWWkWA
7897122075118.537B84143V0050R229038A-3
7811322209122243B84143V0050R229045A-3
78133825010883058B84143V0066R229061A-3
79181231015023064B84143V0075R229072A-3
79230440019043777B84143V0095R229087A-3
80247760018775591B84143V0130S230105A-3
803513550296375126B84143V0162S229145A-3
803718550316890153B84143V0162S229169A-3
8048909003990110187B84143V0230S229206A-3
U
n
= 500 V
72309902193.07.0B84143V0011R22907A6-5
72368902784.010.2B84143V0011R22911A0-5
70401803215.513B84143V0016R229014A-5
756131404737.520B84143V0025R229021A-5
7578516062511.025B84143V0033R229027A-5
789312207111532B84143V0050R229034A-5
78102722080718.535B84143V0050R229040A-5
7812102509602244B84143V0066R229052A-5
78147325012233052B84143V0066R229065A-5
78187031015603761B84143V0075R229077A-5
802625630199545.080B84143V0130S230101A-5
803430630280055.0104B84143V0130S230124A-5
803718550316875.0140B84143V0162S229158A-5
804422550387290.0161B84143V0162S229180A-5
3AXD00000588487
Definitions
P
n
Typical motor power
I
2
Rated current of the drive-filter combination available continuously without
overload at 40 °C.
Noise Noise level is a combined value for the drive and the filter. Heat dissipation
is a value for the filter.
Derating
See section Deratings for special settings in the drive control program (page 167).
Common mode, du/dt and sine filters 229

Table of Contents

Other manuals for ABB ACS880-11

Related product manuals