122 Parameters
03.05 FB A reference 1 Reference 1 received through fieldbus adapter A.
See also chapter Fieldbus control through a fieldbus adapter
(page 569).
-
-100000.00 …
100000.00
Reference 1 from fieldbus adapter A. 1 = 10
03.06 FB A reference 2 Reference 2 received through fieldbus adapter A. -
-100000.00 …
100000.00
Reference 2 from fieldbus adapter A. 1 = 10
03.07 FB B reference 1 Reference 1 received through fieldbus adapter B. -
-100000.00 …
100000.00
Reference 1 from fieldbus adapter B. 1 = 10
03.08 FB B reference 2 Reference 2 received through fieldbus adapter B. -
-100000.00 …
100000.00
Reference 2 from fieldbus adapter B. 1 = 10
03.09 EFB reference 1 Scaled reference 1 received through the embedded fieldbus
interface. The scaling is defined by 58.26 EFB ref1 type.
1 = 10
-30000.00 …
30000.00
Reference 1 received through the embedded fieldbus
interface.
1 = 10
03.10 EFB reference 2 Scaled reference 2 received through the embedded fieldbus
interface. The scaling is defined by 58.27 EFB ref2 type.
1 = 10
-30000.00 …
30000.00
Reference 2 received through the embedded fieldbus
interface.
1 = 10
03.11 DDCS controller ref
1
Reference 1 received from the external (DDCS) controller.
The value has been scaled according to parameter 60.60
DDCS controller ref1 type.
See also section External controller interface (page 39).
1 = 10
-30000.00 …
30000.00
Scaled reference 1 received from external controller. 1 = 10
03.12 DDCS controller ref
2
Reference 2 received from the external (DDCS) controller.
The value has been scaled according to parameter 60.61
DDCS controller ref2 type.
1 = 10
-30000.00 …
30000.00
Scaled reference 2 received from external controller. 1 = 10
03.13 M/F or D2D ref1 Master/follower reference 1 received from the master. The
value has been scaled according to parameter 60.10 M/F ref1
type.
See also section Master/follower functionality (page 31).
1 = 10
-30000.00 …
30000.00
Scaled reference 1 received from master. 1 = 10
03.14 M/F or D2D ref2 Master/follower reference 2 received from the master. The
value has been scaled according to parameter 60.11 M/F ref2
type.
1 = 10
-30000.00 …
30000.00
Scaled reference 2 received from master. 1 = 10
03.30 FB A reference 1
int32
Reference 1 received through fieldbus adapter A as a 32-bit
integer.
-
-2147483648 …
2147483647
Reference 1 from fieldbus adapter A. -
No. Name/Value Description Def/FbEq16