138 Parameters
06.32 MSW bit 13 sel Selects a binary source whose status is transmitted as bit 13
of 06.11 Main status word.
False
False 0. 0
True 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 114). -
06.33 MSW bit 14 sel Selects a binary source whose status is transmitted as bit 14
of 06.11 Main status word.
False
False 0. 0
True 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 114). -
06.36 LSU Status Word (Only visible when supply unit control activated by 95.20)
Shows the status of the supply unit.
See also section Control of a supply unit (LSU) (page 41), and
parameter group 60 DDCS communication.
This parameter is read-only.
-
0000h…FFFFh Supply unit status word. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Description
0 Ready on 1 = Ready to switch on
1 Ready run 1 = Ready to operate, DC link charged
2 Ready ref 1 = Operation enabled
3 Tripped 1 = A fault is active
4…6 Reserved
7 Warning 1 = A warning is active
8 Modulating 1 = The supply unit is modulating
9 Remote 1 = Remote control (EXT1 or EXT2)
0 = Local control
10 Net ok 1 = Supply network voltage OK
11 User bit 0 Selectable in supply control program
12 User bit 1 Selectable in supply control program
13 User bit 2 Selectable in supply control program
14 Charging 1 = Charging circuit active
0 = Charging circuit inactive
15 User bit 3 Selectable in supply control program