Parameters 141
MCW user bit 1 Bit 13 of 06.01 Main control word (see page 130). 3
MCW user bit 2 Bit 14 of 06.01 Main control word (see page 130). 4
MCW user bit 3 Bit 15 of 06.01 Main control word (see page 130). 5
Other [bit] Source selection (see Terms and abbreviations on page 114). -
06.48 Follower CW user
bit 3 selection
Selects a binary source whose status is transmitted as bit 15
of the Follower control word to follower drives. (Bits 0…11 of
the Follower control word are taken from 06.01 Main control
word.)
MCW user bit
3
False 0. 0
True 1. 1
MCW user bit 0 Bit 12 of 06.01 Main control word (see page 130). 2
MCW user bit 1 Bit 13 of 06.01 Main control word (see page 130). 3
MCW user bit 2 Bit 14 of 06.01 Main control word (see page 130). 4
MCW user bit 3 Bit 15 of 06.01 Main control word (see page 130). 5
Other [bit] Source selection (see Terms and abbreviations on page 114). -
06.50 User status word 1 User-defined status word. This word shows the status of the
binary sources selected by parameters 06.6006.75.
This parameter is read-only.
-
0000h…FFFFh User-defined status word. 1 = 1
06.60 User status word 1
bit 0 sel
Selects a binary source whose status is shown as bit 0 of
06.50 User status word 1.
False
False 0. 0
True 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 114). -
06.61 User status word 1
bit 1 sel
Selects a binary source whose status is shown as bit 1 of
06.50 User status word 1.
Out of
window
False 0. 0
True 1. 1
Out of window Bit 3 of 06.19 Speed control status word (see page 135). 2
Other [bit] Source selection (see Terms and abbreviations on page 114). -
06.62 User status word 1
bit 2 sel
Selects a binary source whose status is shown as bit 2 of
06.50 User status word 1.
Emergency
stop failed
False 0. 0
True 1. 1
Emergency stop
failed
Bit 8 of 06.17 Drive status word 2 (see page 133). 2
Other [bit] Source selection (see Terms and abbreviations on page 114). -
No. Name/Value Description Def/FbEq16
Bit Name Description
0 User status bit 0 Status of source selected by parameter 06.60
1 User status bit 1 Status of source selected by parameter 06.61
……
15 User status bit 15 Status of source selected by parameter 06.75