Parameters 171
14.13 DI1 OFF delay (Visible when 14.01 Module 1 type = FDIO-01)
Defines the deactivation delay for digital input DI1. See
parameter 14.12 DI1 ON delay.
0.00 s
0.00 3000.00 s Deactivation delay for DI1. 10 = 1 s
14.13 DIO1 OFF delay (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Defines the deactivation delay for digital input/output DIO1.
See parameter 14.12 DIO1 ON delay.
0.00 s
0.00 3000.00 s Deactivation delay for DIO1. 10 = 1 s
14.14 DIO2 function (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Selects whether DIO2 of the extension module is used as a
digital input or output.
Input
Output DIO2 is used as a digital output. 0
Input DIO2 is used as a digital input. 1
14.16 DIO2 output source (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Selects a drive signal to be connected to digital input/output
DIO2 when parameter 14.14 DIO2 function is set to Output.
For the available selections, see parameter 14.11 DIO1 output
source.
Not
energized
14.17 DI2 ON delay (Visible when 14.01 Module 1 type = FDIO-01)
Defines the activation delay for digital input DI2. See
parameter 14.12 DI1 ON delay.
0.00 s
0.00 3000.00 s Activation delay for DI2. 10 = 1 s
14.17 DIO2 ON delay (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Defines the activation delay for digital input/output DIO2. See
parameter 14.12 DIO1 ON delay.
0.00 s
0.00 3000.00 s Activation delay for DIO2. 10 = 1 s
14.18 DI2 OFF delay (Visible when 14.01 Module 1 type = FDIO-01)
Defines the deactivation delay for digital input DI2. See
parameter 14.12 DI1 ON delay.
0.00 s
0.00 3000.00 s Deactivation delay for DI2. 10 = 1 s
14.18 DIO2 OFF delay (Visible when 14.01 Module 1 type = FIO-01 or FIO-11)
Defines the deactivation delay for digital input/output DIO2.
See parameter 14.12 DIO1 ON delay.
0.00 s
0.00 3000.00 s Deactivation delay for DIO2. 10 = 1 s
14.19 DIO3 function (Visible when 14.01 Module 1 type = FIO-01)
Selects whether DIO3 of the extension module is used as a
digital input or output.
Input
Output DIO3 is used as a digital output. 0
Input DIO3 is used as a digital input. 1
14.19 AI supervision
function
(Visible when 14.01 Module 1 type = FIO-11 or FAIO-01)
Selects how the drive reacts when an analog input signal
moves out of the minimum and/or maximum limits specified
for the input.
The inputs and the limits to be observed are selected by
parameter 14.20 AI supervision selection.
No action
No action No action taken. 0
Fault Drive trips on 80A0 AI supervision.1
Warning Drive generates an A8A0 AI supervision warning. 2
No. Name/Value Description Def/FbEq16