Parameters 265
30.12 Maximum speed Defines the maximum allowed speed.
WARNING! This value must not be lower than 30.11
Minimum speed.
WARNING! In frequency control mode, this limit is not
effective. Make sure the frequency limits (30.13 and
30.14) are set appropriately if frequency control is
used.
WARNING! In a master/follower configuration, do not
set maximum and minimum speed limits with the same
sign on a follower drive. See section Master/follower
functionality (page 31).
1500.00 rpm;
1800.00 rpm
(95.20 b0)
-30000.00 …
30000.00 rpm
Maximum speed. See par.
46.01
30.13 Minimum frequency Defines the minimum allowed frequency.
WARNING! This value must not be higher than 30.14
Maximum frequency.
WARNING! This limit is effective in frequency control
mode only.
-50.00 Hz;
-60.00 Hz
(95.20 b0)
-500.00 … 500.00
Hz
Minimum frequency. See par.
46.02
30.14 Maximum
frequency
Defines the maximum allowed frequency.
WARNING! This value must not be lower than 30.13
Minimum frequency.
WARNING! This limit is effective in frequency control
mode only.
50.00 Hz;
60.00 Hz
(95.20 b0)
-500.00 … 500.00
Hz
Maximum frequency. See par.
46.02
30.15 Maximum start
current enable
A temporary motor current limit specifically for starting can be
defined by this parameter and 30.16 Maximum start current.
When this parameter is set to Enable, the drive observes the
start current limit defined by 30.16 Maximum start current. The
limit is in force for 2 seconds after initial magnetization (of an
asynchronous induction motor) or autophasing (of a
permanent magnet motor), but not more often than once in
every 7 seconds. Otherwise, the limit defined by 30.17
Maximum current is in force.
Note: The availability of a start current higher than the general
limit depends on drive hardware. See the rating data in the
hardware manual of the drive.
Disable
Disable Start current limit disabled. 0
Enable Start current limit enabled. 1
30.16 Maximum start
current
Defines a maximum start current when enabled by parameter
30.15 Maximum start current enable.
-
0.00 … 30000.00 A Maximum start current. 1 = 1 A
30.17 Maximum current Defines the maximum allowed motor current. 0.00 A
0.00 … 30000.00 A Maximum motor current. 1 = 1 A
No. Name/Value Description Def/FbEq16