Parameters 407
Even Even parity indication bit, one stop bit. 1
92.46 Hiperface baud rate (Visible when an absolute encoder is selected)
Defines the transfer rate of the link with a HIPERFACE
encoder.
Typically this parameter need not be set.
4800 bits/s
4800 bits/s 4800 bit/s. 0
9600 bits/s 9600 bit/s. 1
19200 bits/s 19200 bit/s. 2
38400 bits/s 38400 bit/s. 3
92.47 Hiperface node
address
(Visible when an absolute encoder is selected)
Defines the node address for a HIPERFACE encoder.
Typically this parameter need not be set.
64
0…255 HIPERFACE encoder node address. -
93
93 Encoder 2
configuration
Settings for encoder 2.
Notes:
The contents of the parameter group vary according to the
selected encoder type.
It is recommended that encoder connection 1 (group 92
Encoder 1 configuration) is used whenever possible since
the data received through that interface is fresher than the
data received through connection 2 (this group).
93.01 Encoder 2 type Selects the type of encoder/resolver 2. None
configured
None configured None. 0
TTL TTL. Module type (input): FEN-01 (X31), FEN-11 (X41) or
FEN-21 (X51).
1
TTL+ TTL+. Module type (input): FEN-01 (X32). 2
Absolute encoder Absolute encoder. Module type (input): FEN-11 (X42). 3
Resolver Resolver. Module type (input): FEN-21 (X52). 4
HTL HTL. Module type (input): FEN-31 (X82). 5
HTL 1 HTL. Module type (input): FSE-31 (X31). 6
HTL 2 HTL. Module type (input): FSE-31 (X32). Not supported at the
time of publication.
7
93.02 Encoder 2 source Selects the interface module that the encoder is connected to.
(The physical locations and types of encoder interface
modules are defined in parameter group 91 Encoder module
settings.)
Module 1
Module 1 Interface module 1. 1
Module 2 Interface module 2. 2
93.10 Pulses/revolution (Visible when a TTL, TTL+ or HTL encoder is selected)
See parameter 92.10 Pulses/revolution.
2048
93.10 Sine/cosine number (Visible when an absolute encoder is selected)
See parameter 92.10 Sine/cosine number.
0
93.10 Excitation signal
frequency
(Visible when a resolver is selected)
See parameter 92.10 Excitation signal frequency.
1 kHz
93.11 Pulse encoder type (Visible when a TTL, TTL+ or HTL encoder is selected)
See parameter 92.11 Pulse encoder type.
Quadrature
No. Name/Value Description Def/FbEq16