416 Parameters
95.20 HW options word 1 Specifies hardware-related options that require differentiated
parameter defaults. Activating a bit in this parameter makes
the necessary changes in other parameters – for example,
activating an emergency stop option reserves a digital input.
In many cases, the differentiated parameters will also be
write-protected.
This parameter, as well as the changes in other parameters
implemented by it, are not affected by a parameter restore.
WARNING! After switching any bits in this word,
recheck the values of the affected parameters.
Note: This parameter cannot be changed while the drive is
running.
-
0000h…FFFFh Hardware options configuration word 1. 1 = 1
No. Name/Value Description Def/FbEq16
Bit Name Information
0 Supply frequency
60 Hz
0 = 50 Hz; 1 = 60 Hz. Affects parameters 11. 45, 11.59, 12.20, 13.18,
30.11, 30.12, 30.13, 30.14, 31.26, 31.27, 40.15, 40.37, 41.15, 41.37,
46.01, 46.02.
1 Emergency stop
Cat 0
1 = Emergency stop, Category 0, without FSO module. Affects
21.04, 21.05, 23.11.
2 Emergency stop
Cat 1
1 = Emergency stop, Category 1, without FSO module. Affects
10.24, 21.04, 21.05, 23.11.
3 RO2 for -07
cabinet cooling fan
1 = Control of cabinet cooling fan (used only with specific
ACS880-07 hardware). Affects 10.27, 10.28, 10.29.
4 Externally powered
control unit
1 = Control unit powered externally. Affects 95.04. (Only visible with
a ZCU control unit)
5 DC supply switch 1 = DC switch monitoring active. Affects 20.12, 31.03, 95.08. (Only
visible with a ZCU control unit)
6 DOL motor switch 1 = Motor fan control active. Affects 10.24, 35.100, 35.103, 35.104.
7 xSFC-01 fuse
switch controller
1 = xSFC charging controller used. Affects 95.09. (Only visible with a
BCU control unit)
8 Service switch or
PTC/Pt100 relay
1 = Service switch or PTC/Pt100 relay connected. Affects
31.01,
31.02.
9 Output contactor 1 = Output contactor present. Affects 10.24, 20.12.
10 Brake resistor, sine
filter, IP54 fan
1 = Status (eg. thermal) switches connected to DIIL input. Affects
20.11, 20.12.
11 INU-DSU
communication
*1 = Diode supply unit control by inverter unit active. Makes several
parameters visible in groups 06, 60, 61, 62 and 94. (Only visible with
a BCU control unit)
12 Reserved
13 du/dt filter
activation
1 = Active: An external du/dt filter is connected to the drive output.
The setting will limit the output switching frequency. With inverter
module frame sizes R5i to R7i, the fan of the module will be forced to
full speed. Note: This bit is to be left at 0 if the drive/inverter module
is equipped with internal du/dt filtering (for example, frame R8i
inverter modules with option +E205).
14 DOL fan activation 1 = The inverter unit consists of frame R8i modules with direct-on-
line cooling fans (option +C188). Disables fan feedback monitoring
and changes fan control to ON/OFF type.
15 INU-ISU
communication
*1 = IGBT supply unit control by inverter unit active. Affects 31.23
and 95.02. Makes several parameters visible in groups 01, 05, 06,
07, 30, 31, 60, 61, 62, 94 and 96.
*See section Control of a supply unit (LSU) (page 41).