Replacing the LCL filter module with option +H381
See Step-by-step drawings for an installation example of standard drive configuration in
Rittal VX25 800 mm wide enclosure (page 233):
1. Disconnect the LCL filter module from the drive module.
2. Undo the screws that attach the LCL filter module to the enclosure frame.
3. Attach the extraction ramp to the enclosure base with two screws.
4. To prevent the LCL filter module from falling, attach its top lifting lugs with chains to the
enclosure frame.
5. Pull the LCL filter module carefully out of the enclosure preferably with help from another
person.
6. Install the new module in reverse order.