Parameters 421
96.07 Parameter save
manually
Saves the valid parameter values to permanent memory. This
parameter should be used to store values sent from a
fieldbus, or when using an external power supply to the
control board as the supply might have a very short hold-up
time when powered off.
Note: A new parameter value is saved automatically when
changed from the PC tool or control panel but not when
altered through a fieldbus adapter connection.
Done
Done Save completed. 0
Save Save in progress. 1
96.08 Control board boot Changing the value of this parameter to 1 reboots the control
unit (without requiring a power off/on cycle of the complete
drive module).
The value reverts to 0 automatically.
Note: This parameter cannot be changed while the drive is
running.
0
0…1 1 = Reboot the control unit. 1 = 1
96.09 FSO reboot Changing the value of (or the source selected by) this
parameter from 0 to 1 reboots the optional FSO-xx safety
functions module.
Note: The value does not revert to 0 automatically.
False
False 0. 0
True 1. 1
Other [bit] Source selection (see Terms and abbreviations on page 114). -
96.10 User set status Shows the status of the user parameter sets.
This parameter is read-only.
See also section User parameter sets (page 91).
-
n/a No user parameter sets have been saved. 0
Loading A user set is being loaded. 1
Saving A user set is being saved. 2
Faulted Invalid parameter set. 3
User set 1 User set 1 has been loaded. 4
User set 2 User set 2 has been loaded. 5
User set 3 User set 3 has been loaded. 6
User set 4 User set 4 has been loaded. 7