172 Technical data
Terminal data for the drive control unit
See chapter Control unit of frame R11 (page 113).
Electrical power network specification
Voltage (U
1
) ACS880-17-xxxxx-3 drives: 380…415 VAC 3-phase +10%…-15%. This is
indicated in the type designation label as typical input voltage level
3 400 V AC.
ACS880-
17-xxxxx-5 drives: 380…500 VAC 3-phase +10%…-15%. This is
indicated in the type designation label as typical input voltage levels
3 400/480/500 V AC.
ACS880-
17-xxxxx-7 drives: 525…690 VAC 3-phase +10%…-15%. This is
indicated in the type designation label as typical input voltage levels
3 525/600/690 V AC.
Network type TN (grounded) and IT (ungrounded) systems
Frequency (f
1
) 50/60 Hz, Variation ± 5% of nominal frequency
Imbalance Max. ± 3% of nominal phase-to-phase voltage
Short-circuit withstand
strength (IEC 61439-1)
Maximum allowable prospective short-circuit current is 65 kA when the input
cable is protected with gG type fuses (IEC 60269) having maximum operating
time of 0.1 seconds and maximum current rating of 1250 A gG.
Power factor cos phi
1
= 1, cos phi (total) = 0.99
Harmonic distortion THD Total harmonic distortion) current < 0.05 · I
1cont.max
if supply network
voltage is not distorted by other loads and when the drive operates at the
nominal load.
I
1cont.max
is continuous maximum input current of the line-side converter.
The table below shows typical results on indicated networks. The values are
measured at the drive’s input terminals.
R
sc
THD Voltage [%] THD Current [%]
20 3 2.5*
100 1.9 2.5*
THD Total Harmonic Distortion (THD). The voltage THD depends on the short-
circuit ratio (R
sc
). The spectrum of the distortion also contains
interharmonics.
R
sc
I
sc
/I
N
I
sc
short-circuit current at point of common coupling (PCC)
I
N
drive nominal current
* Other loads can influence the THD value.
Motor connection data
Motor types Asynchronous AC induction motors, permanent magnet synchronous motors,
AC induction servomotors, ABB synchronous reluctance (SynRM) motors
Voltage (U
2
) 0 to U
1
, 3-phase symmetrical, This is indicated in the type designation label as
typical output voltage level as 3 0…U
1
, U
max
at the field weakening point
~
~
~
50
2
2
N
n
I
I
I
n
n
th
harmonic component
I
N
nominal current
~